A Brief Guide to AS/NZS 2243-2006
Safety in Laboratories Part 8: Fume Cupboards
The Standard requires that fume cupboards are audited to a checklist. Here is an example checklist with abbreviated description of compliance items.
Control valve handles marked to identify service fluid
Service outlets individually controlled
Service controls outside fume chamber
Electrical outlets outside fume chamber
Electrical outlets protected by RCD's
Emergency Isolator correctly labelled
Fault status audible and visible
Power failure alarm capable of 20 min duration
Fan runs after manual isolation of power & gas
Automatic low airflow isolation of power & gas
Manual restart for power & gas
1 minute delay after fan on before power & gas available
Fan runs for 20 minutes after shut down, and power & gas not available
400 Lx at worktop
Lighting sealed from fumes
Access to service light fitting
Base of fume chamber sealed to contain spills
Spill containment >10mm high, >5L volume
Sash counter-balanced
Sash transparent, corrosion resistant
Sash has mechanical upper stop, needs tool to release, auto reset
Sash lower stop >50mm
Aerodynamic sash handle
Removeable baffles
Support structure suitable for chemicals, load and heat
Warning label fitted
Serial No plate fitted
Thermal sensor (if fitted) corrosion resistant
Minimum 5 air changes / minute through fume chamber
All exhaust duct inside the building at negative pressure
Airflow continuously monitored
Separate duct, own fan
no reverse air flow
Fan accessible for cleaning
Vertical discharge 3m above roof
Fire extinguisher provided at 4m
Fume cupboard performance is determined by velocity test, and tracer smoke evaluation. Average face velocity must be 0.5m/sec or more. The total variation must be within 20% of the mean. Tracer smoke must not escape from the fume chamber.